Thermal-conductivity measurement
Uses the thermal conductivity principle to measure gas content, with a temperature-compensated cell for stable monitoring.
GENERATOR HYDROGEN PURITY ANALYZER
Temperature-compensated thermal conductivity•Protective hydrogen sampling system•Automatic drainage and safety bypass•Ex d IIC T6 Gb
Measurement rangesCO₂ in air / CO₂ in H₂: 0–100%; H₂ in air: 90–100%
Accuracy±2% F.S
Factory 4–20 mA mappingH₂ in air: 90–100%; max load 800 Ω
Sample flow / pressure0.5 SCFH / ≤0.1 MPa
Power supplyAC 90–265 V, 50 Hz; 35 W
Explosion protectionEx d IIC T6 Gb
HOW THE PRODUCT WORKS
The RS-301ON Hydrogen Purity Analyzer is designed for hydrogen-cooled generator sets. It determines gas content using the thermal conductivity principle, with a temperature-compensated thermal-conductivity cell intended to support stable, accurate monitoring as operating temperature varies.
The analyzer is supplied with a hydrogen sampling system that filters oil and moisture from the sample gas to help protect the transmitter during continuous monitoring. The product information also describes a precise sampling arrangement for on-site calibration, automatic drainage, and a safety bypass function. These features support routine operation and service access in generator applications.
The published ranges cover CO₂ in air from 0–100%, CO₂ in H₂ from 0–100%, and H₂ in air from 90–100%. The factory 4–20 mA output is configured for H₂ in air over 90–100%, with a maximum load of 800 Ω. Confirm the required gas-mixture mode and output mapping for your generator and gas-replacement procedure.
The specified sample flow is 0.5 SCFH and the sampling pressure is up to 0.1 MPa. The analyzer accepts AC 90–265 V at 50 Hz, with 35 W power consumption. Its published explosion-protection marking is Ex d IIC T6 Gb. Confirm site classification, sample tubing, interfaces, and applicable certificates as part of project engineering.
For a quotation or configuration review, provide the generator model, gas mixture and measurement mode, sample pressure and flow, power supply, required outputs, installation area classification, and commissioning requirements. This helps configure an online hydrogen purity analyzer for hydrogen-cooled generator operation.
Uses the thermal conductivity principle to measure gas content, with a temperature-compensated cell for stable monitoring.
Measures CO₂ in air, CO₂ in H₂, and H₂ in air in the published ranges; confirm the target mixture and measurement mode for your operating procedure.
The accompanying sampling device is designed to filter oil and moisture from hydrogen samples to help protect the transmitter during continuous service.
The precise sampling arrangement is described as facilitating field calibration; confirm calibration procedure and required gases with the supplier.
Published features include automatic drainage and a safety bypass to support site operation and maintenance.
Developed for hydrogen-cooled generator requirements; review sample conditions, output mapping, and hazardous-area requirements for your installation.
APPLICATIONS
Continuously monitor hydrogen purity and gas composition in hydrogen-cooled power generators.
Use the listed H₂-in-air, CO₂-in-air, and CO₂-in-H₂ ranges to support generator gas replacement monitoring; confirm procedural setpoints for the unit.
Integrate analyzer readings and alarm relay signals into generator monitoring and plant instrumentation, subject to interface review.
| Parameter | Specification |
|---|---|
| Measurement principle | Thermal conductivity with temperature-compensated cell |
| CO₂ in air range | 0–100% |
| CO₂ in H₂ range | 0–100% |
| H₂ in air range | 90–100% |
| Accuracy | ±2% F.S |
| Analog output | 4–20 mA; factory setting corresponds to H₂ in air at 90–100%; maximum load 800 Ω |
| Alarm relay | Contact current: 3 A |
| Sample flow rate | 0.5 SCFH |
| Sampling pressure | ≤0.1 MPa |
| Input voltage | AC 90–265 V, 50 Hz |
| Power consumption | 35 W |
| Explosion-proof marking | Ex d IIC T6 Gb |
| Dimensions (L × W × H) | 800 × 400 × 1660 mm |
| Sampling system | Sample conditioning to filter oil and moisture; automatic drainage and safety bypass stated by manufacturer |
Confirm the measuring range, output, power supply, and process conditions for your application when requesting a quotation.
For a project-specific RS-301ON Hydrogen Purity Analyzer quotation and application review, share your target measurement range, gas composition, operating temperature and humidity, pressure, installation method, required signal output, and project location. This helps our team assess the right configuration for your hydrogen monitoring or gas analysis system.
Send your application detailsFAQ
Find guidance on RS-301ON Hydrogen Purity Analyzer measuring range, installation, operating conditions, and integration with hydrogen monitoring systems.
The published ranges are CO₂ in air at 0–100%, CO₂ in H₂ at 0–100%, and H₂ in air at 90–100%. Confirm which measurement mode is required for your generator and gas-replacement procedure.
The factory setting maps the 4–20 mA output to H₂ in air from 90–100%; maximum load is 800 Ω. Confirm the requested mapping before ordering.
The product information describes sample conditioning that filters oil and moisture from hydrogen to help protect the transmitter. It also lists automatic drainage and a safety bypass.
The published sample flow is 0.5 SCFH and sampling pressure is ≤0.1 MPa. Confirm actual site pressure, tubing, and sample requirements with the technical team.
The listed supply is AC 90–265 V, 50 Hz, with 35 W consumption; the explosion-proof marking is Ex d IIC T6 Gb. Verify the required certificates and site classification.
Share the generator model, gas mixtures and measurement mode, sampling pressure and flow, required output mapping, alarm integration, power supply, installation area classification, and commissioning needs.
Send your operating conditions and project requirements for a technical review and quotation.