NA1000AW Online Hydrogen Detector product image

ONLINE HYDROGEN LEAK DETECTOR

NA1000AW Online Hydrogen Detector

Natural-diffusion sampling•Local display•Concurrent 4–20 mA and RS-485•Relay alarms and sensor diagnostics

Measuring range0–100% LEL / 0–4% Vol

Response time (T90)<30 s

Low / high alarm10% LEL / 40% LEL

Concurrent outputs4–20 mA and two-wire RS-485

Relay output1 active alarm relay; 3 A resistive

ProtectionEx d II C T6 Gb; IP65; SIL 2 stated

HOW THE PRODUCT WORKS

Indoor hydrogen leak detection with local indication and remote signals

Continuous hydrogen leak monitoring for indoor industrial areas

The NA1000AW Online Hydrogen Detector monitors hydrogen in ambient air by natural diffusion. It is designed for indoor industrial environments where a hydrogen leak needs to be detected and reported locally and to a central control room. Applications listed in the product documentation include petroleum, chemical, pharmaceutical, iron and steel, and gas storage facilities.

Local indication with simultaneous control-room signals

Measured concentration is processed by the transmitter and displayed locally. Concurrent outputs include a 4–20 mA analog signal proportional to the selected 0–100% range, two-wire RS-485 communication, and one active alarm relay output. The relay rating is 3 A for resistive loads at 24 VDC, 120 VAC, or 240 VAC. Confirm controller compatibility, cable routing, alarm logic, and output scaling during system design.

Configurable installation and alarm thresholds

The detector supports wall mounting, with pipe-clamp mounting available as an option. The documented low and high alarm setpoints are 10% LEL and 40% LEL. Field calibration concentration can be adjusted by the user. For centralized bus-powered or independent local-power arrangements, confirm the chosen wiring and 24 VDC supply plan for each channel.

Sensor diagnostics and operating conditions

The product documentation describes sensor ageing compensation, sensor-fault identification, over-range protection, power-on self-test, self-diagnosis, and self-recovery. Standard operation is specified from −25 to +60 °C; the catalytic type is specified from −40 to +70 °C. Ambient humidity is below 95% RH, non-condensing. Confirm sensor type, area classification, certification documents, and environmental limits for the actual supplied configuration.

For detector selection or a system quotation, provide the site layout, detection points, expected hydrogen concentration, mounting method, alarm and control-system interfaces, power arrangement, ambient conditions, and required certification. These details help specify a fixed hydrogen detector for indoor industrial leak monitoring.

Key product features

Natural-diffusion hydrogen sampling

Samples ambient air by natural diffusion for indoor hydrogen leak monitoring.

Concurrent analog and digital transmission

Provides 4–20 mA and two-wire RS-485 simultaneously, with an active alarm relay for integration with control-room systems.

Sensor ageing compensation and fault alerts

Product documentation describes automatic compensation for sensor ageing and identification of sensor faults that could affect detection or alarm capability.

Over-range protection and self-diagnostics

Includes automatic over-range protection, power-on self-test, self-diagnosis, and self-recovery functions.

Flexible mounting and power arrangement

Supports wall mounting and optional pipe-clamp mounting; documentation lists centralized bus power or independent local power arrangements.

Field-adjustable calibration concentration

Allows the calibration concentration to be adjusted on site; confirm calibration procedure and target gas requirements with the supplier.

APPLICATIONS

Typical applications

Petroleum and chemical facilities

Monitor indoor hydrogen leak points around process equipment and enclosed work areas.

Pharmaceutical and steel plants

Add hydrogen detection at indoor production, utility, or storage locations where site risk assessment requires it.

Hydrogen storage and industrial sites

Use local readings and remote signals to alert staff and the central control room; determine detector placement through a site survey.

NA1000AW Online Hydrogen Detector technical specifications and integration requirements

ParameterSpecification
Target gasHydrogen (H₂)
Sampling methodNatural diffusion
Measuring range0–100% LEL / 0–4% Vol
Repeatability2%
Span drift±5% F.S
Zero drift<2% F.S
Response time (T90)<30 s
Low alarm setpoint10% LEL
High alarm setpoint40% LEL
Ambient temperatureStandard type: −25 to +60 °C; catalytic type: −40 to +70 °C
Ambient humidity<95% RH, non-condensing
Alarm outputOne active alarm relay; resistive contact load: 3 A at 24 VDC, 120 VAC, or 240 VAC
Communication outputTwo-wire RS-485; shielded twisted-pair cable; maximum distance 1000 m
Analog output4–20 mA proportional to 0–100% range; maximum load 800 Ω; simultaneous with RS-485
Input voltage / power24 VDC ±15%; 2 W per channel
Explosion-proof markingEx d II C T6 Gb (stated in documentation as Exd II CT6 Gb)
Ingress protectionIP65
CertificationExplosion-proof certification and SIL 2 certification stated in product documentation; verify supplied certificates
Recommended shielded cable≥RVVP 4 × 0.75 mm²
Cable outer diameterØ 6–9 mm
InstallationWall mounting; pipe-clamp mounting optional
Dimensions (L × W × H)172.5 × 165.5 × 73 mm
WeightAbout 1 kg

Confirm the measuring range, output, power supply, and process conditions for your application when requesting a quotation.

What to include in your inquiry

For a project-specific NA1000AW Online Hydrogen Detector quotation and application review, share your target measurement range, gas composition, operating temperature and humidity, pressure, installation method, required signal output, and project location. This helps our team assess the right configuration for your hydrogen monitoring or gas analysis system.

Send your application details

FAQ

Frequently asked questions about NA1000AW Online Hydrogen Detector selection and applications

Find guidance on NA1000AW Online Hydrogen Detector measuring range, installation, operating conditions, and integration with hydrogen monitoring systems.

01

How does the NA1000AW sample hydrogen?

It uses natural diffusion to sample ambient air in indoor environments; it is not a pumped sample-draw arrangement according to the supplied documentation.

02

What measuring range and alarm points are specified?

The documented range is 0–100% LEL / 0–4% Vol. Low and high alarm setpoints are 10% LEL and 40% LEL, respectively.

03

Can analog and digital outputs be used at the same time?

The product document specifies concurrent 4–20 mA output and two-wire RS-485 communication, together with one active alarm relay. Confirm controller compatibility and output scaling.

04

Which temperature rating should I use?

Standard operation is specified from −25 to +60 °C; the catalytic type is specified from −40 to +70 °C. Confirm which sensor type and temperature range apply to the offered configuration.

05

What mounting and power options are available?

Wall mounting is listed, with pipe-clamp mounting optional. The document lists 24 VDC ±15% input and 2 W per channel and notes centralized bus or independent local power arrangements.

06

What should I include in an inquiry?

Provide the site and detection-point layout, expected hydrogen range, sensor type, mounting preference, alarm logic, RS-485 or 4–20 mA interfaces, power plan, ambient conditions, and required certificates.